このエントリーをはてなブックマークに追加


ID 34051
フルテキストURL
著者
Fujita, Hideki Okayama University
Akagi, Hirofumi Okayama University
抄録

A design strategy for the combined power filter for a three-phase twelve-pulse thyristor rectifier is proposed. The shunt passive filter, which can minimize the output voltage of the series active filter, is designed and tested in a prototype model. A specially designed shunt passive filter makes it possible to reduce the required rating of the series active filter to 60% compared with a conventional shunt passive filter

キーワード
active filters
passive filters
rectifying circuits
thyristor applications
備考
Digital Object Identifier: 10.1109/IAS.1991.178344
Published with permission from the copyright holder. This is the institute's copy, as published in Industry Applications Society Annual Meeting, 1991., Conference Record of the 1991 IEEE, 28 Sept.-4 Oct. 1991, Volume 1, Pages 898 - 903.
Publisher URL:http://dx.doi.org/10.1109/IAS.1991.178344
Copyright © 1991 IEEE. All rights reserved.
発行日
1991-10
出版物タイトル
Industry Applications Society Annual Meeting
1巻
資料タイプ
学術雑誌論文
言語
英語
査読
有り
DOI
Submission Path
electrical_engineering/2