抄録

This paper focuses on a shunt active filter based on the detection of harmonic voltages at the point of installation. The objective of the active filter is to attenuate harmonic propagation resulting from series/parallel resonance between capacitors for power factor correction and line inductors in a power distribution line. The active filter acts as a low resistor to the external circuit for harmonic frequencies, and it is installed on the end bus of the power distribution line, just like a 50 Ω terminator installed on the end terminal of a signal transmission line. Therefore, the function of the active filter is referred to as “harmonic termination” in this paper. Experimental results obtained from a laboratory system rated at 200 V and 20 kW verify that the active filter for the purpose of harmonic termination has the capability of harmonic damping throughout the power distribution line

キーワード
active filters
harmonic distortion
power distribution lines
power harmonic filters
power system harmonics