Akagi, Hirofumi
Okayama University
Fujita, Hideaki
Okayama University
Wada, Keiji
Okayama University
|
| 抄録 | This paper focuses on a shunt active filter based on the detection of harmonic voltages at the point of installation. The objective of the active filter is to attenuate harmonic propagation resulting from series/parallel resonance between capacitors for power factor correction and line inductors in a power distribution line. The active filter acts as a low resistor to the external circuit for harmonic frequencies, and it is installed on the end bus of the power distribution line, just like a 50 Ω terminator installed on the end terminal of a signal transmission line. Therefore, the function of the active filter is referred to as “harmonic termination” in this paper. Experimental results obtained from a laboratory system rated at 200 V and 20 kW verify that the active filter for the purpose of harmonic termination has the capability of harmonic damping throughout the power distribution line |
| キーワード | active filters
harmonic distortion
power distribution lines
power harmonic filters
power system harmonics
|
| 備考 | Digital Object Identifier: 10.1109/28.767015
Published with permission from the copyright holder. This is the institute's copy, as published in Industry Applications, IEEE Transactions on, May-June 1999, Volume 35, Issue 3, Pages 638-645. Publisher URL:http://dx.doi.org/10.1109/28.767015 Copyright © 1999 IEEE. All rights reserved. |
| 発行日 | 1999-6
|
| 出版物タイトル |
Industry Applications
|
| 巻 | 35巻
|
| 号 | 3号
|
| 開始ページ | 638
|
| 終了ページ | 645
|
| 資料タイプ |
学術雑誌論文
|
| 言語 |
英語
|
| 査読 |
有り
|
| DOI | |
| Submission Path | electrical_engineering/68
|