抄録 | A method for analysing the current distribution in high-T/sub c/ superconducting (HTS) power cable is examined by the aid of the novel use of anisotropic conductivity and 3-D finite element method considering E-J power law characteristic. The detailed current distribution in the cable is illustrated and the shielding effect of HTS shield layer with intervals is also examined. It is shown that AC losses in shield layer with intervals are increased when the interval between wires becomes large.
|
キーワード | E-J power law characteristic
HTS power cable
HTS shield
3-D finite element analysis
|
備考 | Digital Object Identifier: 10.1109/TASC.2004.830019
Published with permission from the copyright holder. This is the institute's copy, as published in Applied Superconductivity, IEEE Transactions on, June 2004, Volume 14, Issue 2, Pages 654-657. Publisher URL:http://dx.doi.org/10.1109/TASC.2004.830019 Copyright © 2004 IEEE. All rights reserved. |