麻酔用ガス(ether及びcyclopropane)の爆発防止に関する基礎的研究 第2篇 etherガス及びcyclopropaneの爆発限界と室内環境とに関する研究

坂下 昇 岡山大学医学部衛生学教室
69_715.pdf 1.8 MB
発行日
1957-03-31
抄録
The influences of temperature and humidity in the operating room on the lower explosive limit were studied and the relation of the indoor air conditioning to the precaution against ignition was clarified. 1) By raising the temparature of the mixed gases of ether or cyclopropane with the air from 8°C to 30°C. the lower explosive limits went straightly from 2.27% to 1.84% in case of ether gas and from 2.6% to 2.38% in case of cyclopropane. Thus the danger of ignition increased. 2) In the highest humidity of the mixed gases of ether or cyclopropane with the air, the extent of the explosive limits increased about 0.11% in case of ether gas and about 0.07% in case of cyclopropane than in the lowest humidity. Thus the tendency of explosion increased, but the difference was not so marked.
ISSN
0030-1558
NCID
AN00032489