このエントリーをはてなブックマークに追加
ID 15688
JaLCDOI
Sort Key
7
FullText URL
Author
Himei Toyoji
Nakanishi Senichiro
Komatubara Hitoshi
Kawata Sigeo
Onishi Fujio
Tabuchi Takashi
Abstract
When a transformer is energized, the inrush of abnormally high magnetizing current may be noted for a short time until normal flux conditions are established. This may cause the failure of a protective relay, so many preventives are usually accepted for the purpose of normal relay performance. The authors, instead, now have tried to control the inrush current itself, by means of the soft starting method using two reverse parallel thyristors. In this paper, the method to control the inrush current itself, is presented by the soft-starting method using thyristors. The experimental results of this Method verifies the good controlability of the transient magnetic flux of a transformer and then the availability of the control of magnetizing inrush current in the cases of a single phase connection and a three phase one.
Publication Title
Memoirs of the School of Engineering, Okayama University
Published Date
1976-01-27
Volume
volume10
Issue
issue2
Publisher
岡山大学工学部
Publisher Alternative
School of Engineering, Okayama University
Start Page
45
End Page
54
ISSN
0475-0071
NCID
AA00733903
Content Type
Departmental Bulletin Paper
OAI-PMH Set
岡山大学
language
English
File Version
publisher
NAID
Eprints Journal Name
mfe