Akagi, Hirofumi
Fujita, Hideaki
Wada, Keiji
|
| Abstract | This paper focuses on a shunt active filter based on the detection of harmonic voltages at the point of installation. The objective of the active filter is to attenuate harmonic propagation resulting from series/parallel resonance between capacitors for power factor correction and line inductors in a power distribution line. The active filter acts as a low resistor to the external circuit for harmonic frequencies, and it is installed on the end bus of the power distribution line, just like a 50 Ω terminator installed on the end terminal of a signal transmission line. Therefore, the function of the active filter is referred to as “harmonic termination” in this paper. Experimental results obtained from a laboratory system rated at 200 V and 20 kW verify that the active filter for the purpose of harmonic termination has the capability of harmonic damping throughout the power distribution line |
| Keywords | active filters
harmonic distortion
power distribution lines
power harmonic filters
power system harmonics
|
| Note | Digital Object Identifier: 10.1109/28.767015
Published with permission from the copyright holder. This is the institute's copy, as published in Industry Applications, IEEE Transactions on, May-June 1999, Volume 35, Issue 3, Pages 638-645. Publisher URL:http://dx.doi.org/10.1109/28.767015 Copyright © 1999 IEEE. All rights reserved. |
| Published Date | 1999-6
|
| Publication Title |
Industry Applications
|
| Volume | volume35
|
| Issue | issue3
|
| Start Page | 638
|
| End Page | 645
|
| Content Type |
Journal Article
|
| language |
English
|
| Refereed |
True
|
| DOI | |
| Submission Path | electrical_engineering/68
|